Energies, Vol. 19, Pages 82: Dynamic Multi-Output Stacked-Ensemble Model with Hyperparameter Optimization for Real-Time Forecasting of AHU Cooling-Coil Performance
Energies, Vol. 19, Pages 82: Dynamic Multi-Output Stacked-Ensemble Model with Hyperparameter Optimization for Real-Time Forecasting of AHU Cooling-Coil Performance
Energies doi: 10.3390/en19010082
Authors:
Md Mahmudul Hasan
Pasidu Dharmasena
Nabil Nassif
This study introduces a dynamic, multi-output stacking framework for real-time forecasting of HVAC cooling-coil behavior in air-handling units. The dynamic model encodes short-horizon system memory with input/target lags and rolling psychrometric features and enforces leakage-free, time-aware validation. Four base learners—Random Forest, Bagging (DT), XGBoost, and ANN—are each optimized with an Optuna hyperparameter tuner that systematically explores architecture and regularization to identify data-specific, near-optimal configurations. Their out-of-fold predictions are combined through a Ridge-based stacker, yielding state-of-the-art accuracy for supply-air temperature and chilled water leaving temperature (R2 up to 0.9995, NRMSE as low as 0.0105), consistently surpassing individual models. Novelty lies in the explicit dynamics encoding aligned with coil heat and mass-transfer behavior, physics-consistent feature prioritization, and a robust multi-target stacking design tailored for HVAC transients. The findings indicate that this hyperparameter-tuned dynamic framework can serve as a high-fidelity surrogate for cooling-coil performance, supporting set-point optimization, supervisory control, and future extensions to virtual sensing or fault-diagnostics workflows in industrial AHUs.