Energies, Vol. 19, Pages 669: A Full-Time-Domain Analysis Based Method for Fault Transient Characteristic and Optimization Control in New Distribution System
Energies doi: 10.3390/en19030669
Authors:
Wanxing Sheng
Xiaoyu Yang
Dongli Jia
Keyan Liu
Chengfeng Li
Qing Han
In new distribution systems with high penetration of renewable energy, inverter-based sources exhibit significant differences in fault characteristics compared to traditional power sources due to the absence of a constant electromotive force and their operation under nonlinear control links, rendering conventional fault current calculation methods inadequate. To address these challenges, a full-time-domain analysis-based method for modelling and calculating fault transient characteristics is proposed. First, a dynamic model of inverter-based sources accounting for current loop saturation effects is established, and phase plane analysis is employed to resolve nonlinear control regions. On this basis, a full-time-domain fault current calculation method is proposed, wherein the steady-state operating point after a fault is determined by iteratively solving the network node voltage equations. By integrating control strategies and derived transient differential equations, the fault current expression across the full-time-domain scope is formulated. Furthermore, a multi-objective optimization control strategy is proposed to achieve effective fault current suppression, and an improved Simulated Annealing-Particle Swarm Optimization (SA-IPSO) hybrid algorithm is adopted for efficient solution. Finally, SIMULINK-based simulation experiments validate the accuracy and effectiveness of the proposed method in transient characteristic analysis and current suppression.